DSE L401 MK-II

Features:



Lighting Tower Controller

DSE L401 MKII is an intelligent control module designed specifically for mobile lighting tower applications. The control module provides class leading flexible features that are fully configurable to suit multiple complex lighting sequences.

Application : Engine driven Mobile Lighting Tower

Brands:DSE

Description

DSE L401 MKII is an intelligent control module designed specifically for mobile lighting tower applications. The control module provides class leading flexible features that are fully configurable to suit multiple complex lighting sequences.

PRODUCT HIGHLIGHTS


I/O
– Configurable digital inputs (6)
– Configurable analogue / digital inputs (3)
– Configurable DC outputs (8)
– Independent fuel and start outputs
– Configurable staged light control outputs

COMMUNICATIONS
– USB for PC configuration

ENGINE COMPATIBILITY
– CAN engine support (Tier 4F / Stage 5)
– Conventional engine support (MPU & Hz)

CONFIGURATION
– DSE Configuration Suite PC software
– Front panel (PIN protected)

ADVANCED FEATURES
– Fuel monitoring allows automatic ‘selected lights off’ to enable longer running hours
– DC alternator compatibility
– Lighting tower mast and holding support control
– Automatic & manual light control
– Automatic light sequencing
– Individual lighting control
– Configurable light re-strike timer
– Light failure detection
– Sophisticated engine monitoring and protections
– 8 event scheduler and 4-stage load output, protects the generator from stalling on start-up
– Heated display option

Protection Functions

  • Engine speed protection Under / Over Speed (with MPU only)
  • Low Oil Pressure (Sensor / Switch input)
  • High Coolant (Water) Temperature (Sensor / Switch input)
  • Low Fuel Level (Sensor / Switch input)
  • Emergency Stop
  • Charger Alternator Fail
  • Low / High Battery Voltage

Variant

  • L401-01 – L401 MKII Intelligent Lighting Tower Control Module (Rtc)

Hardware

  • Dimension Detail

OVERALL SIZE : 140 mm x 113 mm x 43 mm
PANEL CUTOUT SIZE : 118 mm x 92 mm

  • DC SUPPLY

CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous

CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking.

MAXIMUM OPERATING CURRENT
85 mA at 12 V, 96 mA at 24 V

MAXIMUM STANDBY CURRENT
51 mA at 12 V, 47 mA at 24 V

MAXIMUM SLEEP CURRENT
35 mA at 12 V, 32 mA at 24 V

MAXIMUM DEEP SLEEP CURRENT
<10 uA at 12 V, <10 uA at 24 V

  • OUTPUTS

OUTPUT A (FUEL)
10 A short term, 5 A continuous,
at supply voltage

OUTPUT B (START)
10 A short term, 5 A continuous,
at supply voltage

AUXILIARY OUTPUTS C to J
2 A DC at supply voltage ­­

  • GENERATOR

VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)

FREQUENCY RANGE
3.5 Hz to 75 Hz

Standards

Connection Diagram