DSE E100

Features:



ENGINE ONLY CONTROLLER 

DSE E100 is an Engine only Controller has built-in analog Sensors for oil pressure, coolant temperature, fuel level monitoring along with start / Stop.

Application : Engine driven pumps and compressors.

Brands:DSE

Description

DSE E100 is an easy to use non electronic (Conventional) engine only controller designed to provide flexible control with built in monitoring and protection.

PRODUCT HIGHLIGHTS

I/O
– Configurable analogue / digital inputs (3)
– Configurable digital inputs (4)
– Configurable remote start input
– Configurable DC outputs (4)
– Fuel and start outputs

 

COMMUNICATIONS
– USB for PC configuration
– DSEWebNet® compatible

 

ENGINE COMPATIBILITY
– Conventional engine support (MPU & W terminal)

 

CONFIGURATION
– DSE Configuration Suite PC software
– Front panel (PIN protected)

 

ADVANCED FEATURES
– 3 engine maintenance alarms
– Engine speed protection
– Comprehensive warning, controlled shut down or shut down protection on fault condition
– Engine hours counter
– Real-time clock for accurate event logging
– Engine pre-heat
– Engine run-time scheduler
– Battery voltage monitoring
– Large display screen
– Power save mode
– Start on low battery voltage

 

 

 

Protection Functions

  • Engine speed protection Under / Over Speed (with MPU only)
  • Low Oil Pressure (Sensor / Switch input)
  • High Coolant (Water) Temperature (Sensor / Switch input)
  • Low Fuel Level (Sensor / Switch input)
  • Emergency Stop
  • Charger Alternator Fail
  • Low / High Battery Voltage

Hardware

  • Dimension Details:

    • Over All Dimension – 140 mm x 113 mm x 43 mm
    • Panel Cut Out Dimension – 118 mm x 92 mm
  • DC SUPPLY

    CONTINUOUS VOTLAGE RATING
    8 V to 35 V continuous

    CRANKING DROPUTS
    Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries.

    MAXIMUM OPERATING CURRENT
    85 mA at 12 V, 96 mA at 24 V

    MAXIMUM STANDBY CURRENT
    51 mA at 12 V, 47 mA at 24 V

    MAXIMUM SLEEP CURRENT
    35 mA at 12 V, 32 mA at 24 V

    CHARGE FAIL/EXCITATION RANGE
    0 V to 35 V

  • INPUTS

    DIGITAL INPUTS A to D
    Negative switching

    ANALOGUE INPUTS A to C
    Configurable as:
    Negative switching digital input
    Resistive

  • OUTPUTS

    DC OUTPUT A (FUEL) & B (START)
    10 A short-term
    5 A continuous at supply voltage

    VOLT-FREE OUTPUTS C & D
    2 A DC at supply voltage

    AUXILIARY OUTPUTS C, D, E & F
    2 A DC at supply voltage

    PULSE PICK-UP

    VOLTAGE RANGE
    +/- 0.5 V to 70 V

    FREQUENCY RANGE
    5 Hz to 10,000 Hz

Standards

Connection Diagram